APC Smart-UPS commands
din niste notite vechi, ca sa nu se piarda…
| command | meaning |
| Y | enter “smart” mode |
| U | simulate power failure |
| D | start calibration cycle (works only if battery charge considered 100%) |
| W | perform self-test |
| E | set automatic self-test interval |
| B | query battery voltage |
| f | query battery charge level, % |
| j | query estimated runtime on battery |
| P | query load ratio (current load to unit’s rated max load) |
| C | query internal temperature |
| L | query input voltage |
| O | query output voltage |
| M | query max line voltage since unit reset |
| N | query min line voltage since unit reset |
| l (lowercase L) | set lower admissible line voltage |
| u | set upper admissible line voltage |
| e | set battery charge level prior to powering the load |
| r | set wakeup delay |
| s | set unit sensitivity (high/medium/low) |
| q | set “low battery” signaling level, in estimated runtime minutes |
| o | set lowest battery admissible voltage |
| p | set shutdown delay (time since UPS shutdown command) |
| n | queries some number (unit serial?) |
| G |
queries cause of last transfer to batteries. returns:
|
| X |
query self-test result. returns:
|
vote:@echo off
rem replace COM1 with your relevant com port number
net stop ups
mode COM1 baud=2400 parity=n data=8 stop=1 to=off xon=off dtr=off rts=off idsr=off
echo D>COM1
net start ups
December 16th, 2008 at 04:45
I Have just replaced Battery in my Smart-UPS 1000,but Battery Led are flashing.
How to do normal ups?
thanks
Reply
vv reply on December 22nd, 2008:
charge it to the maximum, then calibrate.
repeat about 5 times.
Reply